| Communications interface | 10BASE-T or 100BASE-TX (auto-sensing) |
| Communication protocols | ARP, UDP, TCP, ICMP, Telnet, TFTP, AutoIP, DHCP, HTTP, SNMP |
| Connector | RJ45 |
| Compatibility | Ethernet: Version 2.0/IEEE 802.3 |
| Number of devices that can be connected | 1 to 4 SLAVE devices, idle current max. 6 mA |
| Baud rate | 300 - 9600 bps |
| Protection | - overvoltage protection TVS 600W |
- electronic protection against overloads and short circuit on the communication line |
note: converter can withstand sustained short circuit on the communication line |
| Galvanic separation | up to 1kV from power supply, more than 1kV from Ethernet |
| Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
| Recommended range of power supply voltages |
| DC power supply | 8V to 28V |
| Maximum limits of supply voltage - permanent operation at these voltages is not recommended |
| Minimum DC power | 7.5V - minimal voltage necessary for the operation of the converter |
| Maximum DC power | 30V - above this the overvoltage protection will activate |
| Protection | overvoltage protection TVS 600W |
| Power consumption | 1.3W to 1.9W. Depends on M-Bus line load and communication. |
| Maximum consumption during M-Bus line short is 2.2W. |
| Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
| Power - green | indication of connected supply voltage |
| Transmit - green | indication of data broadcasting on the M-Bus line |
| Receive - yellow | indication of data reception on the M-Bus line |
| Overload/Short - red | indication of M-Bus line overload – flashing (idle current > 8mA) |
| indication of short on the M-Bus line – turned on (resistance of the line < 500Ω) |
| Operating range | -20°C to 50°C |
| Mechanical design | plastic box |
| Mounting | 35 mm DIN rail (EN 50022 top hat rail) |
| Dimensions: height x width x length | 58 x 36 x 95mm |
| Protection classification | IP20 |
| Weight | 72g |
EMC compatibility of the M-Bus converter has been tested according to the following industrial environment standards.
| Standard | Test | Level |
| EN 55011 | Power line - CONDUCTED EMISSIONS 10/150 kHz - 30 MHz | Class A |
| EN 55011 | RADIATED EMISSIONS (Electric Field) 30 MHz - 1000 MHz | Class A |
| |
| Standard | Test | Level |
| EN 61000-4-2 | ELECTROSTATIC DISCHARGE (ESD) - Contact discharge | ± 4 kV |
| EN 61000-4-2 | ELECTROSTATIC DISCHARGE (ESD) - Air discharge | ± 8 kV |
| EN 61000-4-4 | ELECTRICAL FAST TRANSIENT/BURST - Power line | ± 4 kV |
| EN 61000-4-4 | ELECTRICAL FAST TRANSIENT/BURST - M-Bus line | ± 4 kV |
| EN 61000-4-5 | SURGE IMMUNITY - Power line. Common/differential mode. | ± 1 kV / ± 0.5 kV |
| EN 61000-4-5 | SURGE IMMUNITY - M-Bus line. Cable shielding. | ± 4 kV |
| EN 61000-4-5 | SURGE IMMUNITY - M-Bus line. Common/differential mode.* | ± 2 kV / ± 1 kV |
| EN 61000-4-6 | CONDUCTED DISTURBANCES, INDUCED BY RADIO-FREQUENCY | 10 V |
| FIELDS 0.15MHz - 80 MHZ. Power line and M-Bus line. |
* test carried out at the request of the manufacturer.
The M-Bus port has an increased durability against overvoltage. Carrying out this type of test is not required with the use of shield cable.